All LED off

- No power on the unit

Step 1

Remove the reset task house... measure the voltage between pin 1 and 2 to be between 18 and 31,2 Vdc... if voltage is ok- remove the measuring head...
and replace the 3,15 A fuse.

Necessary parts used in the fault locating procedure:

Step 1: Fuse 3,15 A 11058 Replacement of fuse

Step 2

Replace the measuring head with an exchange unit!

Necessary parts used in the fault locating procedure:

Step 2: Exchange measuring head ** Replacing of measuring head



**Please check your model description for correct part number under “SPARE PARTS”!


.